Fire Safety Engineering for Design – Gaseous Fixed Fire Extinguishing Systems – Part 314
November 23, 2026 9:59 amLWF’s Fire Safety Engineering blog series is written for Architects, building designers and others in the construction industry to highlight and promote discussion on all topics around fire engineering. In part 313, LWF talked about halocarbon and fluoroketone extinguishing agents. In part 314, we discuss HF-227ea and HFC-125.
HFC-227ea and HFC-125 have been widely used in gaseous fire suppression systems, particularly in buildings and facilities where water-based extinguishing systems could cause significant damage to sensitive equipment. Both are hydrofluorocarbons (HFCs), commonly described as clean agents because they suppress fires without leaving residue.
HFC-227ea, also known by the trade name FM-200, is heptafluoropropane. HFC-125, sometimes marketed as Ecaro-25, is pentafluoroethane. Both agents have been used in applications such as computer rooms, data centres, telecommunications facilities, control rooms and other areas containing valuable electrical or electronic equipment.
Their firefighting effectiveness is generally attributed to two mechanisms. Approximately 80% of the extinguishing effect is understood to come from heat absorption, which reduces the temperature of the fire below the level needed to sustain combustion. The remaining 20% is attributed to chemical inhibition, involving fluorine-containing species that interfere with the chain reactions responsible for maintaining a flame.
This combination allows the agents to extinguish fires rapidly when the correct concentration is achieved. Their clean discharge characteristics also offer practical advantages. Unlike powder or foam systems, they do not leave deposits that require extensive cleaning or risk contaminating sensitive equipment. Successful operation depends on correct system design, adequate agent concentration and the ability of the protected enclosure to retain the gas for the required period.
The environmental impact of HFC-227ea and HFC-125 has become a major consideration in their continued use. Both are classified as fluorinated greenhouse gases (F-gases), substances controlled because of their contribution to global warming. Their global warming potentials are particularly high. Using the figures published by the UK Government, HFC-227ea has a GWP of 3,220, while HFC-125 has a GWP of 3,500. These figures mean that one kilogram of either gas has the same warming potential as thousands of kilograms of carbon dioxide over the relevant assessment period. The figures and chemical classifications are published in the UK Government’s F-gas guidance.
Environmental controls place responsibilities on organisations operating systems containing these gases. In the UK, stationary fire protection equipment is subject to F-gas leak-checking requirements. The inspection frequency depends on the quantity of gas expressed as tonnes of carbon dioxide equivalent. For HFC-227ea, for example, a system containing 1.6 kg reaches the five-tonne threshold requiring leak checks at least every 12 months. Larger installations require more frequent inspections, and automatic leak detection is mandatory at 500 tonnes of CO2 equivalent or above, subject to the applicable exemptions.
Operators must also arrange prompt repairs when leaks are identified and retain the required maintenance records. The Environment Agency and DEFRA set out these obligations.
Discharge testing presents a further challenge. Deliberately releasing these gases for routine testing creates an avoidable environmental impact and is inconsistent with the objective of preventing unnecessary emissions. Maintenance and inspection procedures therefore focus on non-discharge testing, including cylinder pressure or weight checks, control panel testing, detection system verification, actuator inspections and checks of the associated pipework and components. The condition of the protected enclosure must also be assessed to ensure it can retain the extinguishing concentration. Operators should follow the applicable regulatory requirements and manufacturers’ maintenance instructions.
Spain provides an example of how environmental taxation can influence the market for these systems. Its environmental tax on fluorinated greenhouse gases calculates the rate using a coefficient of 0.015 multiplied by the gas’s global warming potential, subject to a maximum of €100 per kilogram. The tax increases the financial implications of using high-GWP agents and has contributed to the commercial pressure surrounding new installations.
The regulatory position is also evolving internationally. The EU’s revised F-gas Regulation (EU) 2024/573, which came into force in March 2024, strengthens controls on fluorinated greenhouse gases and introduces further restrictions on equipment containing high-GWP substances.
For organisations operating existing HFC-227ea or HFC-125 systems, the priority is to maintain effective fire protection while meeting environmental responsibilities. System condition, leakage history, maintenance costs, gas availability and future regulatory requirements should all feature in regular reviews.
When specifying replacement equipment or designing new fire protection installations, lower-GWP alternatives deserve serious consideration. The decision must still account for the hazards present, the sensitivity of the protected equipment, occupancy requirements and the performance of the proposed extinguishing agent. Fire protection cannot be compromised in pursuit of environmental targets, but continuing to install high-GWP agents without assessing alternatives is becoming increasingly difficult to justify.
In part 315 of LWF’s series on fire engineering we will talk about HFC-23 and FK-5-1-12. In the meantime, if you have any questions about this blog, or wish to discuss your own project with one of our fire engineers, please contact us.