Fire Safety for Healthcare Premises - Venting of Basements - Part 61

Posted by LWF: 12/02/2019 11:20

In LWFs blog series for healthcare professionals, the aim is to give information on best practice of fire safety in hospitals and other healthcare premises. In part 60 of this series, the placement of fire hydrants in relation to hospital buildings was discussed. In part 61, we will look at the effects of smoke on basement levels and the use of venting.

A fire which starts in a basement or involves a basement level causes additional complications to a fire on any above ground level. The products of combustion – heat, smoke, airborn particles and other gases – naturally rise and the only escape they often find is stairways. The filling of stairways with hot smoke makes access difficult for the Fire Service. 

Venting of basement areas is therefore an important fire protection measure which can reduce the problem of smoke filling the stairway to basement levels by improving visibility and lowering the temperature.

Vents to open air mean that the smoke and heat can escape more easily and they can be used by the fire service to let cooler air into the basement as required. Smoke outlets to the open air should be provided from every basement storey except where it has a floor area of less than 200 m2 or where it is not more than 3 metres below the adjacent ground level.

The positioning of smoke outlets within the basement space should be considered in order for them to be effective. They should be positioned at a high level, be evenly distributed around the perimeter of the building and discharge into open air outside the building.

In each basement compartment or sub-compartment, the combined cross-sectional area of all smoke outlets should be not less than 2.5% of the floor area of that compartment or sub-compartment.

Where the smoke outlet terminates in a position that is not readily accessible, it must be kept unobstructed and covered with a metal grille or louvre to avoid it becoming covered or blocked accidentally, which would mean the smoke could not vent from that outlet.

Where the smoke outlet terminates in a position that is accessible, it should be covered with a suitably indicated panel or pavement light which can be broken out or opened at will.

Smoke outlets should not affect the use of escape routes and so planning in this regard will be necessary.

In part 62 of this series, LWF will consider the mechanical extraction of smoke from basement levels and the construction of outlet ducts and shafts, before beginning an overview of Firecode (HTM 05-03: Operational Provisions). In the meantime, if you have any questions about this blog, or wish to discuss your own project with one of our fire engineers, please contact us.

Lawrence Webster Forrest has been working with their clients for over 25 years to produce innovative and exciting building projects. If you would like further information on how LWF and fire strategies could assist you, please contact Peter Gyere on 020 8668 8663.

While care has been taken to ensure that information contained in LWF's publications is true and correct at the time of publication, changes in circumstances after the time of publication may impact on the accuracy of this information.

Leave a reply

  *

  *

 


CAPTCHA Image

[ Change the image ]


*Required

Subscribe to our fire safety blogs

Bulletins
Email Format
* indicates required

FIRE SAFETY BLOGS

  • Fire Engineering Design and Risk Assessment - Firefighting & External Water Supplies - Part 27

    In LWF’s Fire Engineering blog series for Architects and others in the building design business, we have been looking at fire safety engineering. In part 26, we looked at how the choice of fire hydrant can affect the efficiency of delivery and by working out the additional time required to prime an underground hydrant when compared to a pillar hydrant with instantaneous couplings, it was established there could be as much as 2 minutes delay...

    Read more...

  • Fire Safety for Healthcare Premises - Venting of Basements - Part 61

    In LWFs blog series for healthcare professionals, the aim is to give information on best practice of fire safety in hospitals and other healthcare premises. In part 60 of this series, the placement of fire hydrants in relation to hospital buildings was discussed. In part 61, we will look at the effects of smoke on basement levels and the use of venting.A fire which starts in a basement or involves a basement level causes...

    Read more...

  • Facilities Management & Fire Safety - Insurers & Property Protection - Part 8

    In LWF’s blog series for those who work in Facilities Management or who have an interest in or responsibility for fire safety, we have been looking at the part Insurers have played in property protection over the years. In part 7, we discussed the role the FOC played in producing rules and regulations not only for building standards but also for fire protection products. In part 8, we will continue looking at the impact of...

    Read more...

  • Fire Engineering Design and Risk Assessment - Firefighting & External Water Supplies - Part 26

    In LWF’s fire engineering blog series for Architects and other interested parties in the building design business, we have been looking at firefighting. In part 25, we looked at how hydrants should be located in relation to the building perimeter and the likely position of a Fire Service pump upon attending a fire at the premises. In part 26, we continue looking at location and also the type of hydrant provided in relation to the...

    Read more...

  • Fire Safety for Healthcare Premises - Fire Mains - Part 60

    In LWFs blog series for healthcare professionals, the aim is to give information on best practice of fire safety in hospitals and other healthcare premises. In part 59 of this series, LWF discussed the requirements for healthcare buildings with a hospital street and which do not require a fire-fighting shaft. In part 60, we will look at the provision of fire mains.Fire mains must be provided in every firefighting shaft, or in some instances,...

    Read more...

Case Studies

The Wohl Neuroscience Institute - Fire Safety, Strategy & Engineering
Key Facts: Client: King’s Clinical Neuroscience Institute Project Manager: MACE Ltd Designers: Devereux Architects/Allies and Morrison Approximate Size: 7,400m2 Description of the Project:...

Read more..

General Bulletins

Fire - The External Risk
When we consider fire safety, our focus is normally from within, what can we do to prevent the occurrence of fire and how we can limit its damage.  Whilst this is the correct stance to take, we m...

Read more..

Technical Bulletins

Evacuation Modelling - Factor in Human Behaviour
Evacuation of buildings can be analyzed in different ways. Approved Document B (ADB) which provides guidance on meeting the requirements of the England and Wales Building Regulations with regard to fi...

Read more..

Site map | Web development London