Fire Safety for Healthcare Premises - Travel Distances & Hospital Streets - Part 20

Posted by LWF: 02/05/2018 14:52

In LWF’s blog series for healthcare professionals, we look to give information on best practice in fire safety for hospitals and other healthcare premises. In part 19 of this series, the principle of keeping the distance to be travelled by any person from the potential point of fire origin to a place of safety was discussed. It is important that these distances are considered and limited in order to maximise the chances of a prompt and safe evacuation. In part 20, we look at what total maximum travel distances are laid out and must be adhered to before discussing Hospital Streets.

The total travel distance from any point within a compartment to either each of two adjoining compartments or an adjoining compartment and a stairway or final exit must be no more than 60 metres. 

Where the point of origin is within a sub-compartment, the total travel distance must be no more than 30 metres to an adjoining compartment/sub-compartment or to a stairway or final exit.

Hospital Streets


The requirements in respect of hospital streets are to enable it to function on a day-to-day basis and also as a major route in a fire situation. It must meet certain requirements in order to fulfil these needs.

A hospital street must be comprised of the same fire-resistant construction as a compartment and should have a minimum clear width of 3 metres at all points.

The street must be divided into a minimum of three sub-compartments, each measuring no longer than 30 metres. This requirement maximises the amount of time it is resistant to fire as each compartment is fire resistant for only a certain amount of time. The passage of building occupants from one sub-compartment to the next means that the clock is ‘reset’ in terms of safety from an existing fire for those individuals.

At ground floor level, the hospital street should have a minimum of two final exits which are located at each extremity of the street and it should be ensured that the maximum travel distance between final exits is no more than 180 metres, as measured along hospital street. The maximum travel distance from any compartment exit onto hospital street to a final exit should be no more than 90 metres.

In part 21 of this series, LWF will continue looking at hospital streets before moving on to discuss the width of escape routes. In the meantime, if you have any questions about this blog, or wish to discuss your own project with one of our fire engineers, please contact us.

Lawrence Webster Forrest has been working with their clients for over 25 years to produce innovative and exciting building projects. If you would like further information on how LWF and fire strategies could assist you, please contact Peter Gyere on 020 8668 8663.

While care has been taken to ensure that information contained in LWF's publications is true and correct at the time of publication, changes in circumstances after the time of publication may impact on the accuracy of this information.

Leave a reply

  *

  *

 


CAPTCHA Image

[ Change the image ]


*Required

Subscribe to our fire safety blogs

Bulletins
Email Format
* indicates required

FIRE SAFETY BLOGS

  • Fire Safety for Healthcare Premises - Vertical Escape - Part 23

    In LWF’s blog series for healthcare professionals, we look to give information on best practice in fire safety for hospitals and other healthcare premises. In part 22 of this series, we looked at the issue of vertical escape in relation to stairways and ascertained that in effect, all stairways in a hospital must be considered escape stairways as they would be used for escape in case of fire. In part 23, we will continue looking...

    Read more...

  • Facilities Management & Fire Safety - Inspection, Testing and Maintenance - Part 1

    In LWF’s blog series for Facilities Managers or those with an interest in or responsibility for fire safety, we aim to give an overview of best practice and methods of applying or maintaining fire prevention provision. In part 1, the importance of inspection, testing and maintenance of fire protection measures is discussed.Once fire protection measures are installed in a building, it would be comforting to think that they were simply waiting in case they...

    Read more...

  • Fire Engineering Design and Risk Assessment - Foam Proportioning - Part 4

    In LWF’s fire engineering blog series for Architects and others in the building design business, we have been looking at fire suppression systems and in particular, foam systems. In part 3, it was ascertained that foam proportioning is the means by which foam concentrate is mixed with water at the necessary ratio. An overview of inductors (also known as line proportioners) was given. In...

    Read more...

  • Fire Safety for Healthcare Premises - Vertical Escape - Part 22

    In LWF’s blog series for healthcare professionals, the aim is to give information on best practice of fire safety in hospitals and other healthcare premises. In part 21 of this series, LWF looked at the necessary considerations of hospital streets and escape route widths. In part 22, we will look at vertical escape using stairways.While it is possible for organisations to denote certain staircases as escape stairs (and therefore, certain staircases are not classed...

    Read more...

  • Fire Engineering Design and Risk Assessment - Foam Systems - Part 3

    In LWF’s Fire Engineering blog series for Architects and others in the building design business, we have been looking at fire suppression systems and, in particular, foam concentrate systems. In part 2, we began an overview of the different types of foam concentrate and part 3 will continue from that point before discussing foam proportioning.Synthetic, or high expansion foam is produced from detergents and, as a result, can produce great quantities of ‘bubbles’ making...

    Read more...

Case Studies

The Wohl Neuroscience Institute - Fire Safety, Strategy & Engineering
Key Facts: Client: King’s Clinical Neuroscience Institute Project Manager: MACE Ltd Designers: Devereux Architects/Allies and Morrison Approximate Size: 7,400m2 Description of the Project:...

Read more..

General Bulletins

Fire - The External Risk
When we consider fire safety, our focus is normally from within, what can we do to prevent the occurrence of fire and how we can limit its damage.  Whilst this is the correct stance to take, we m...

Read more..

Technical Bulletins

Evacuation Modelling - Factor in Human Behaviour
Evacuation of buildings can be analyzed in different ways. Approved Document B (ADB) which provides guidance on meeting the requirements of the England and Wales Building Regulations with regard to fi...

Read more..

Site map | Web development London