Fire Safety for Healthcare Premises - Travel Distances & Hospital Streets - Part 20

Posted by LWF: 02/05/2018 14:52

In LWF’s blog series for healthcare professionals, we look to give information on best practice in fire safety for hospitals and other healthcare premises. In part 19 of this series, the principle of keeping the distance to be travelled by any person from the potential point of fire origin to a place of safety was discussed. It is important that these distances are considered and limited in order to maximise the chances of a prompt and safe evacuation. In part 20, we look at what total maximum travel distances are laid out and must be adhered to before discussing Hospital Streets.

The total travel distance from any point within a compartment to either each of two adjoining compartments or an adjoining compartment and a stairway or final exit must be no more than 60 metres. 

Where the point of origin is within a sub-compartment, the total travel distance must be no more than 30 metres to an adjoining compartment/sub-compartment or to a stairway or final exit.

Hospital Streets


The requirements in respect of hospital streets are to enable it to function on a day-to-day basis and also as a major route in a fire situation. It must meet certain requirements in order to fulfil these needs.

A hospital street must be comprised of the same fire-resistant construction as a compartment and should have a minimum clear width of 3 metres at all points.

The street must be divided into a minimum of three sub-compartments, each measuring no longer than 30 metres. This requirement maximises the amount of time it is resistant to fire as each compartment is fire resistant for only a certain amount of time. The passage of building occupants from one sub-compartment to the next means that the clock is ‘reset’ in terms of safety from an existing fire for those individuals.

At ground floor level, the hospital street should have a minimum of two final exits which are located at each extremity of the street and it should be ensured that the maximum travel distance between final exits is no more than 180 metres, as measured along hospital street. The maximum travel distance from any compartment exit onto hospital street to a final exit should be no more than 90 metres.

In part 21 of this series, LWF will continue looking at hospital streets before moving on to discuss the width of escape routes. In the meantime, if you have any questions about this blog, or wish to discuss your own project with one of our fire engineers, please contact us.

Lawrence Webster Forrest has been working with their clients for over 25 years to produce innovative and exciting building projects. If you would like further information on how LWF and fire strategies could assist you, please contact Peter Gyere on 020 8668 8663.

While care has been taken to ensure that information contained in LWF's publications is true and correct at the time of publication, changes in circumstances after the time of publication may impact on the accuracy of this information.

Leave a reply

  *

  *

 


CAPTCHA Image

[ Change the image ]


*Required

Subscribe to our fire safety blogs

Bulletins
Email Format
* indicates required

FIRE SAFETY BLOGS

  • Fire Engineering Design and Risk Assessment - Compartmentation & Fire Severity - Part 10

    In LWF’s Fire Engineering blog series for Architects and others in the building design industry, we have been looking at the use of compartmentation to avoid the spread of fire. In part 9, the use of compartments with sprinkler systems was discussed and in part 10, we look at the potential severity of fires in enclosed spaces.The severity of a fire in an enclosed space is dependent upon factors such as heat leaving the...

    Read more...

  • Fire Safety for Healthcare Premises - Sprinklers - Part 44

    In LWF’s blog series for healthcare professionals, the aim is to give information on best practice of fire safety in hospitals and other healthcare premises. In part 43 of this series, we discussed cavity barriers and those areas where they are not practical for use, for fire safety reasons. In part 44, we move on to discuss the use of sprinklers in healthcare buildings. Sprinklers are not a requirement for patient areas of healthcare buildings...

    Read more...

  • Facilities Management & Fire Safety - Fire Safety Engineering - Part 1

    In LWF’s blog series for those who work in Facilities Management or who have an interest in or responsibility for fire safety, we were looking at fire safety training. In Part 1 of this series, however, we begin to review the subject of fire safety engineering. While most people reading on this subject could work out what fire safety engineering is, from the title, LWF will start by looking at the history of fire safety...

    Read more...

  • Fire Engineering Design and Risk Assessment - Compartmentation & Sprinklers - Part 9

    In LWF’s fire engineering blog series for Architects and others in the building design business, we have been looking at compartmentation and how can be used both in prescriptive and fire engineered solutions. In part 8 of this series, the provision of a fire safety strategy for a building was discussed and in part 9, we move onto how compartmentation and sprinklers work together.The effectiveness of sprinkler systems at controlling fires has had a...

    Read more...

  • Fire Safety for Healthcare Premises - Cavity Barriers and Sprinklers - Part 43

    In LWF’s blog series for healthcare professionals, the aim is to give information on best practice of fire safety in hospitals and other healthcare premises. In part 42 of this series, we looked at how cavity barriers should be installed in uninterrupted concealed spaces or cavities and also some exceptions to the rules. In part 43, we will continue looking at the use of cavity barriers in healthcare buildings.There are some instances where cavity...

    Read more...

Case Studies

The Wohl Neuroscience Institute - Fire Safety, Strategy & Engineering
Key Facts: Client: King’s Clinical Neuroscience Institute Project Manager: MACE Ltd Designers: Devereux Architects/Allies and Morrison Approximate Size: 7,400m2 Description of the Project:...

Read more..

General Bulletins

Fire - The External Risk
When we consider fire safety, our focus is normally from within, what can we do to prevent the occurrence of fire and how we can limit its damage.  Whilst this is the correct stance to take, we m...

Read more..

Technical Bulletins

Evacuation Modelling - Factor in Human Behaviour
Evacuation of buildings can be analyzed in different ways. Approved Document B (ADB) which provides guidance on meeting the requirements of the England and Wales Building Regulations with regard to fi...

Read more..

Site map | Web development London