Fire Safety for Healthcare Premises - Internal Fire Spread through Structure - Part 33

Posted by LWF: 31/07/2018 12:03

In LWF’s blog series for healthcare professionals, the aim is to give information on best practice of fire safety in hospitals and other healthcare premises. In part 32 of this series, we began to look at the potential for internal fire spread through the structure, including how the load-bearing elements of a building are required to have a minimum period of fire resistance to prevent collapse. In part 33, LWF continues to look at structural elements in terms of fire resistance.

While structural elements such as columns, beams, load-bearing walls and floors must be fire-resistant for a minimum period to avoid the potential for load-bearing failure, it may not be necessary for roof structures and those elements which support only the roof.

A roof may not require fire-resistance for life safety purposes unless it meets one of the following criteria:
- The building stability depends upon the roof
- The roof itself also serves as a floor, as would be the case with a rooftop car park or plantroom
- The roof is used as an escape route

The minimum period of fire-resistance for a given element should be as follows:
Single-storey healthcare buildings must have 30 minutes minimum fire resistance whether or not sprinklers are in place.

Healthcare buildings up to 12m above ground or with basements up to 10m deep should have 60 minutes fire-resistance, reduced to 30 minutes fire-resistance where sprinklers are in place, except in the case of basements.

Healthcare buildings with storeys over 12m above ground or with basements more than 10m deep should have 90 minutes fire-resistance un-sprinklered and 60 minutes sprinklered.

Healthcare buildings with storeys over 30m in height are not permitted to be un-sprinklered and have a minimum fire resistance of 90 minutes when sprinklered.

Where references to sprinklered buildings are made, this must be read as a reference to a life safety sprinkler system suitable for purpose, installed and maintained as per BS EN 12845. (https://shop.bsigroup.com/ProductDetail/?pid=000000000030337104) In addition, it should be noted that in order to reduce the fire-resistance minimum duration of elements of a structure, the entire building must be sprinkler protected. Partial sprinkler coverage cannot provide the same level of protection for structural elements.

While partial sprinkler coverage cannot provide a reason to reduce the minimum fire-resistance of structural elements of the building, it may still be a useful provision for the fire safety design, as it can help to mitigate localised fire risks and offer other fire design benefits. A fire design should be undertaken by a Fire Engineer to provide a solution based on fire-engineering evidence.

In part 34, LWF will discuss compartmentation in healthcare venues. In the meantime, if you have any questions about this blog, or wish to discuss your own project with one of our fire engineers, please contact us.

Lawrence Webster Forrest has been working with their clients for over 25 years to produce innovative and exciting building projects. If you would like further information on how LWF and fire strategies could assist you, please contact Peter Gyere on 020 8668 8663.

While care has been taken to ensure that information contained in LWF's publications is true and correct at the time of publication, changes in circumstances after the time of publication may impact on the accuracy of this information.

Leave a reply

  *

  *

 


CAPTCHA Image

[ Change the image ]


*Required

Subscribe to our fire safety blogs

Bulletins
Email Format
* indicates required

FIRE SAFETY BLOGS

  • Fire Engineering Design and Risk Assessment - Compartmentation - Part 1

    In LWF’s blog series for architects and others in the building design business, we talk about fire engineered and prescriptive solutions for use in England and Wales. In part 1 of this series, we discuss compartmentation of buildings for fire safety purposes.Without effective compartmentation, fire would simply be able to move through a building using the structure as fuel to grow very quickly. Compartmentation is the sub-dividing of a building using fire resisting walls...

    Read more...

  • Fire Safety for Healthcare Premises - Compartmentation - Part 35

    In LWF’s blog series for healthcare professionals, the aim is to give information on best practice of fire safety in hospitals and other healthcare premises. In part 34 of this series, we looked at the role of compartmentation in limiting the spread of fire from one area to another for at least the minimum period of fire resistance required. It was ascertained that this would allow evacuation from the area of fire origin to a...

    Read more...

  • Facilities Management & Fire Safety - Special Duties in the Fire Procedures - Part 9

    In LWF’s blog series for those people who work in Facilities Management, or who have an interest in or responsibility for Fire Safety, we have been looking at what should be contained within an organisation’s Fire Procedures. In part 8 of the series, the duties of a fire warden were discussed. In part 9, the process of accounting for occupants in case of a fire will be outlined.An effective evacuation is one where each...

    Read more...

  • Fire Engineering Design and Risk Assessment - Water Mist System Components - Part 15

    In LWF’s Fire Engineering blog series for Architects and others involved in building design, we have been looking at methods of fire suppression and most recently, water mist systems. In part 14, the basis for design was discussed and in part 15, those components which go into making a water mist system are outlined. Water mist nozzles are primarily designed to generate the very fine droplets of water necessary and to provide momentum for delivery...

    Read more...

  • Fire Safety for Healthcare Premises - Compartmentation - Part 34

    In LWF’s blog series for healthcare professionals, the aim is to give information on best practice of fire safety in hospitals and other healthcare premises. In part 33 of this series, we looked at the potential for fire spread through the internal structure of the building, particularly the minimum periods of fire resistance provided by elements of the structure. In part 34, the use of compartmentation is discussed.Compartmentation is provided by the fire-resistance of...

    Read more...

Case Studies

The Wohl Neuroscience Institute - Fire Safety, Strategy & Engineering
Key Facts: Client: King’s Clinical Neuroscience Institute Project Manager: MACE Ltd Designers: Devereux Architects/Allies and Morrison Approximate Size: 7,400m2 Description of the Project:...

Read more..

General Bulletins

Fire - The External Risk
When we consider fire safety, our focus is normally from within, what can we do to prevent the occurrence of fire and how we can limit its damage.  Whilst this is the correct stance to take, we m...

Read more..