Fire Safety for Healthcare Premises - In-Patient Mental Health & Learning Disability Facilities continued - Part 11

Posted by LWF: 01/03/2018 11:17

Fire Safety for Healthcare premises is a blog series by LWF which aims to give guidance on healthcare-based standards and best practice in fire safety. In part 10 of this series, the additional fire safety measures required for in-patient mental health and learning disability facilities was outlined, particularly in relation to the dual demands of fire safety and security. In part 11, specific design requirements for such facilities are considered.

In order to protect sleeping patients, sleeping and day quarters should be compartmented separately. Sleeping accommodation should comprise bedrooms, bathrooms/WCs, cleaners room, a small office for overnight duty staff and linen storage only. Any other elements of the department must be in other compartments.

Sleeping quarters should be sub-compartmented and each sub-compartment should contain no more than 10 beds, including any swing bed provision (short-term use beds). 

If swing beds may be moved between male and female sub-compartments, the number in each must number no more than 10.

Where it is necessary to maintain segregation of patients during an evacuation, the routes should be designed with such processes in mind. This process should also be taken into account in the design of secure places of safety from fire outside the building and after evacuation.

All bedrooms must be classed as fire hazard rooms and where it is necessary to have rooms which can be locked from the inside, the doors must be fitted with a lock not requiring a key. Any door which can be locked from the inside must be accessible by staff with a standard key, to avoid any delays in opening the door in a fire situation.

As in the case of all healthcare facilities, some patients who have restricted mobility may require moving on their beds and evacuation routes must take the movement of beds as a part of the evacuation process. 

Where bed evacuation is likely, the corridors including junctions and turning spaces must be designed in order that both the bed and the staff members involved in moving the bed can negotiate the space easily. This involves the corridors being of sufficient width to do so. Specific guidance on corridor widths including handrails and doorways is provided in Health Building Note 00-04 – ‘Circulation and communication spaces’. 

Potential alternatives to the guidance given are possible if evidence is provided by an architect and approved by the client, building control officer and fire officer.  Additionally, alternative methods of evacuation may be possible where it can be shown that the proposed plan recognises the limited mobility of the patients and provides a design solution enabling staff to safely manage the evacuation.

In cases where communal bathrooms are provided, these must be classed as fire hazard rooms.

In part 12 of this series, LWF will look at the effective separation of areas accessed by patients from other parts of the premises. In the meantime, if you have any queries about fire safety in healthcare premises or wish to discuss this blog series, please contact Peter Gyere in the first instance on 0208 668 8663.

Lawrence Webster Forrest is a fire engineering consultancy based in Surrey with over 25 years' experience, which provides a wide range of consultancy services to professionals involved in the design, development and construction and operation of buildings. 

While care has been taken to ensure that information contained in LWF's publications is true and correct at the time of publication, changes in circumstances after the time of publication may impact on the accuracy of this information.


Leave a reply

  *

  *

 


CAPTCHA Image

[ Change the image ]


*Required

Subscribe to our fire safety blogs

Bulletins
Email Format
* indicates required

FIRE SAFETY BLOGS

  • Fire Engineering Design and Risk Assessment - Compartmentation & Life Safety - Part 5

    In LWF’s Fire Engineering blog series for Architects and others working in the building design business, we have been discussing compartmentation. In part 4 of this series, the ways in which compartmentation supports life safety functions in a fire situation were summarised. In part 5, we look at the ways the issue of compartmentation and life safety is covered in the national building regulations, before looking at the spread of fire. 

    Read more...

  • Fire Safety for Healthcare Premises - Compartmentation & Fire Hazard Rooms and Areas - Part 39

    In LWF’s blog series for healthcare professionals, the aim is to give information on best practice of fire safety in hospitals and other healthcare premises. In part 38 of this series, the importance of fire stopping the joints between fire separating elements such as walls and any openings was discussed. In part 39, we will continue in that area by looking at fire hazard rooms and areas.While most types of buildings require the protection...

    Read more...

  • Facilities Management & Fire Safety - Content of Fire Training - Part 13

    In LWF’s blog series for those who work in Facilities Management, or who have an interest in or responsibility for Fire Safety, we have been looking at the necessity for staff training and fire drills. In part 12 we looked at the implications of committing to fire safety training in a business or organisation in terms of time commitment. In part 13, the necessary content of the fire safety training sessions is outlined. All comprehensive...

    Read more...

  • Fire Engineering Design and Risk Assessment - Maintenance of Compartmentation - Part 4

    In LWF’s Fire Engineering blogs for Architects and others who work in the building design business, we have been looking at compartmentation of buildings to avoid fire spread from the compartment of fire origin to any other area. In part 3 of this series, the fire-resisting performance of elements which go into comprising a fire-resistant compartment was discussed. In part 4, we discuss how a compartment’s integrity is only as good as its ongoing maintenance,...

    Read more...

  • Facilities Management & Fire Safety - Staff Training & Fire Drills - Part 12

    In LWF’s blog series for those who work in Facilities Management, or who have an interest in or responsibility for fire safety, we have been looking at staff training and fire drills. In part 11 of this series, methods of training were discussed and in part 12, we will continue from that point to discuss the practicalities of who should receive training and how it should be organised.Adequate fire training should be given to...

    Read more...

Case Studies

The Wohl Neuroscience Institute - Fire Safety, Strategy & Engineering
Key Facts: Client: King’s Clinical Neuroscience Institute Project Manager: MACE Ltd Designers: Devereux Architects/Allies and Morrison Approximate Size: 7,400m2 Description of the Project:...

Read more..

General Bulletins

Fire - The External Risk
When we consider fire safety, our focus is normally from within, what can we do to prevent the occurrence of fire and how we can limit its damage.  Whilst this is the correct stance to take, we m...

Read more..

Technical Bulletins

Evacuation Modelling - Factor in Human Behaviour
Evacuation of buildings can be analyzed in different ways. Approved Document B (ADB) which provides guidance on meeting the requirements of the England and Wales Building Regulations with regard to fi...

Read more..

Site map | Web development London