Fire Safety for Healthcare Premises - Hospital Streets & Escape Route Widths - Part 21

Posted by LWF: 10/05/2018 11:00

In LWF’s blog series for healthcare professionals, we look to give information on best practice in fire safety for hospitals and other healthcare premises. In part 20 of this series, we looked at what total maximum travel distances are laid out and must be adhered to, before beginning to look at the requirements for Hospital Streets in terms of fire protection and construction. In part 21, we will continue looking at Hospital Streets before discussing the width of escape routes.

At upper levels, hospital street should provide access to a minimum of two stairways in separate sub-compartments, located so that the maximum distance between the stairways does not exceed 60 metres and the maximum single direction of travel within the street does not exceed 15 metres. The distance from a compartment exit to a stairway via hospital street is no more than 30 metres. The distance between the exit and the stairway should contain no other accommodation aside from sanitary accommodation.

Compartment doorways into hospital street should not be located in the same compartment as entrances to stairways and lifts and should always be located so that an alternative means of escape from each compartment is possible.

Stairways should be placed so that the maximum travel distance from the stairway enclosure to a final exit is no more than 60 metres. The Fire Service will have additional requirements for access to hospital street and these should be provided for as appropriate.

On upper storeys, stairways should be provided in two of the three sub-compartments and the third sub-compartment must be able to accommodate all occupants of the largest adjoining compartment, along with all associated beds and medical equipment.

As well as taking into account the travel distances to final exits, the width of escape routes must also be considered. In the case of healthcare departments where beds and patient trolleys should be moved during an evacuation, the width of the circulation space must be adequate to allow this to happen, along with any staff members moving the bed or trolley or holding equipment used by the patient. 

In other areas, the width of the escape route should be determined by the potential number of people using that route in an emergency. Stairs must also be avoided in any circulation area and any changes in level should be overcome using ramps.

In those areas where beds or trolleys will not be in use, the minimum clear width of an escape route must be 1200 mm for up to 200 people and an additional 275mm for each additional 50 people.

In part 22 of this series, LWF will discuss vertical escape. In the meantime, if you have any queries about fire safety in healthcare premises or wish to discuss this blog series, please contact Peter Gyere in the first instance on 0208 668 8663.

Lawrence Webster Forrest is a fire engineering consultancy based in Surrey with over 25 years' experience, which provides a wide range of consultancy services to professionals involved in the design, development and construction and operation of buildings. 

While care has been taken to ensure that information contained in LWF's publications is true and correct at the time of publication, changes in circumstances after the time of publication may impact on the accuracy of this information.

Leave a reply

  *

  *

 


CAPTCHA Image

[ Change the image ]


*Required

Subscribe to our fire safety blogs

Bulletins
Email Format
* indicates required

FIRE SAFETY BLOGS

  • Fire Engineering Design and Risk Assessment - Compartmentation - Part 1

    In LWF’s blog series for architects and others in the building design business, we talk about fire engineered and prescriptive solutions for use in England and Wales. In part 1 of this series, we discuss compartmentation of buildings for fire safety purposes.Without effective compartmentation, fire would simply be able to move through a building using the structure as fuel to grow very quickly. Compartmentation is the sub-dividing of a building using fire resisting walls...

    Read more...

  • Fire Safety for Healthcare Premises - Compartmentation - Part 35

    In LWF’s blog series for healthcare professionals, the aim is to give information on best practice of fire safety in hospitals and other healthcare premises. In part 34 of this series, we looked at the role of compartmentation in limiting the spread of fire from one area to another for at least the minimum period of fire resistance required. It was ascertained that this would allow evacuation from the area of fire origin to a...

    Read more...

  • Facilities Management & Fire Safety - Special Duties in the Fire Procedures - Part 9

    In LWF’s blog series for those people who work in Facilities Management, or who have an interest in or responsibility for Fire Safety, we have been looking at what should be contained within an organisation’s Fire Procedures. In part 8 of the series, the duties of a fire warden were discussed. In part 9, the process of accounting for occupants in case of a fire will be outlined.An effective evacuation is one where each...

    Read more...

  • Fire Engineering Design and Risk Assessment - Water Mist System Components - Part 15

    In LWF’s Fire Engineering blog series for Architects and others involved in building design, we have been looking at methods of fire suppression and most recently, water mist systems. In part 14, the basis for design was discussed and in part 15, those components which go into making a water mist system are outlined. Water mist nozzles are primarily designed to generate the very fine droplets of water necessary and to provide momentum for delivery...

    Read more...

  • Fire Safety for Healthcare Premises - Compartmentation - Part 34

    In LWF’s blog series for healthcare professionals, the aim is to give information on best practice of fire safety in hospitals and other healthcare premises. In part 33 of this series, we looked at the potential for fire spread through the internal structure of the building, particularly the minimum periods of fire resistance provided by elements of the structure. In part 34, the use of compartmentation is discussed.Compartmentation is provided by the fire-resistance of...

    Read more...

Case Studies

The Wohl Neuroscience Institute - Fire Safety, Strategy & Engineering
Key Facts: Client: King’s Clinical Neuroscience Institute Project Manager: MACE Ltd Designers: Devereux Architects/Allies and Morrison Approximate Size: 7,400m2 Description of the Project:...

Read more..

General Bulletins

Fire - The External Risk
When we consider fire safety, our focus is normally from within, what can we do to prevent the occurrence of fire and how we can limit its damage.  Whilst this is the correct stance to take, we m...

Read more..

Technical Bulletins

Evacuation Modelling - Factor in Human Behaviour
Evacuation of buildings can be analyzed in different ways. Approved Document B (ADB) which provides guidance on meeting the requirements of the England and Wales Building Regulations with regard to fi...

Read more..

Site map | Web development London