Fire Safety for Healthcare Premises - Hospital Streets & Escape Route Widths - Part 21

Posted by LWF: 10/05/2018 11:00

In LWF’s blog series for healthcare professionals, we look to give information on best practice in fire safety for hospitals and other healthcare premises. In part 20 of this series, we looked at what total maximum travel distances are laid out and must be adhered to, before beginning to look at the requirements for Hospital Streets in terms of fire protection and construction. In part 21, we will continue looking at Hospital Streets before discussing the width of escape routes.

At upper levels, hospital street should provide access to a minimum of two stairways in separate sub-compartments, located so that the maximum distance between the stairways does not exceed 60 metres and the maximum single direction of travel within the street does not exceed 15 metres. The distance from a compartment exit to a stairway via hospital street is no more than 30 metres. The distance between the exit and the stairway should contain no other accommodation aside from sanitary accommodation.

Compartment doorways into hospital street should not be located in the same compartment as entrances to stairways and lifts and should always be located so that an alternative means of escape from each compartment is possible.

Stairways should be placed so that the maximum travel distance from the stairway enclosure to a final exit is no more than 60 metres. The Fire Service will have additional requirements for access to hospital street and these should be provided for as appropriate.

On upper storeys, stairways should be provided in two of the three sub-compartments and the third sub-compartment must be able to accommodate all occupants of the largest adjoining compartment, along with all associated beds and medical equipment.

As well as taking into account the travel distances to final exits, the width of escape routes must also be considered. In the case of healthcare departments where beds and patient trolleys should be moved during an evacuation, the width of the circulation space must be adequate to allow this to happen, along with any staff members moving the bed or trolley or holding equipment used by the patient. 

In other areas, the width of the escape route should be determined by the potential number of people using that route in an emergency. Stairs must also be avoided in any circulation area and any changes in level should be overcome using ramps.

In those areas where beds or trolleys will not be in use, the minimum clear width of an escape route must be 1200 mm for up to 200 people and an additional 275mm for each additional 50 people.

In part 22 of this series, LWF will discuss vertical escape. In the meantime, if you have any queries about fire safety in healthcare premises or wish to discuss this blog series, please contact Peter Gyere in the first instance on 0208 668 8663.

Lawrence Webster Forrest is a fire engineering consultancy based in Surrey with over 25 years' experience, which provides a wide range of consultancy services to professionals involved in the design, development and construction and operation of buildings. 

While care has been taken to ensure that information contained in LWF's publications is true and correct at the time of publication, changes in circumstances after the time of publication may impact on the accuracy of this information.

Leave a reply

  *

  *

 


CAPTCHA Image

[ Change the image ]


*Required

Subscribe to our fire safety blogs

Bulletins
Email Format
* indicates required

FIRE SAFETY BLOGS

  • Fire Engineering Design and Risk Assessment - Compartmentation & Fire Severity - Part 10

    In LWF’s Fire Engineering blog series for Architects and others in the building design industry, we have been looking at the use of compartmentation to avoid the spread of fire. In part 9, the use of compartments with sprinkler systems was discussed and in part 10, we look at the potential severity of fires in enclosed spaces.The severity of a fire in an enclosed space is dependent upon factors such as heat leaving the...

    Read more...

  • Fire Safety for Healthcare Premises - Sprinklers - Part 44

    In LWF’s blog series for healthcare professionals, the aim is to give information on best practice of fire safety in hospitals and other healthcare premises. In part 43 of this series, we discussed cavity barriers and those areas where they are not practical for use, for fire safety reasons. In part 44, we move on to discuss the use of sprinklers in healthcare buildings. Sprinklers are not a requirement for patient areas of healthcare buildings...

    Read more...

  • Facilities Management & Fire Safety - Fire Safety Engineering - Part 1

    In LWF’s blog series for those who work in Facilities Management or who have an interest in or responsibility for fire safety, we were looking at fire safety training. In Part 1 of this series, however, we begin to review the subject of fire safety engineering. While most people reading on this subject could work out what fire safety engineering is, from the title, LWF will start by looking at the history of fire safety...

    Read more...

  • Fire Engineering Design and Risk Assessment - Compartmentation & Sprinklers - Part 9

    In LWF’s fire engineering blog series for Architects and others in the building design business, we have been looking at compartmentation and how can be used both in prescriptive and fire engineered solutions. In part 8 of this series, the provision of a fire safety strategy for a building was discussed and in part 9, we move onto how compartmentation and sprinklers work together.The effectiveness of sprinkler systems at controlling fires has had a...

    Read more...

  • Fire Safety for Healthcare Premises - Cavity Barriers and Sprinklers - Part 43

    In LWF’s blog series for healthcare professionals, the aim is to give information on best practice of fire safety in hospitals and other healthcare premises. In part 42 of this series, we looked at how cavity barriers should be installed in uninterrupted concealed spaces or cavities and also some exceptions to the rules. In part 43, we will continue looking at the use of cavity barriers in healthcare buildings.There are some instances where cavity...

    Read more...

Case Studies

The Wohl Neuroscience Institute - Fire Safety, Strategy & Engineering
Key Facts: Client: King’s Clinical Neuroscience Institute Project Manager: MACE Ltd Designers: Devereux Architects/Allies and Morrison Approximate Size: 7,400m2 Description of the Project:...

Read more..

General Bulletins

Fire - The External Risk
When we consider fire safety, our focus is normally from within, what can we do to prevent the occurrence of fire and how we can limit its damage.  Whilst this is the correct stance to take, we m...

Read more..

Technical Bulletins

Evacuation Modelling - Factor in Human Behaviour
Evacuation of buildings can be analyzed in different ways. Approved Document B (ADB) which provides guidance on meeting the requirements of the England and Wales Building Regulations with regard to fi...

Read more..

Site map | Web development London