Fire Engineering Design and Risk Assessment - Water Mist System Components - Part 15

Posted by LWF: 08/08/2018 9:55

In LWF’s Fire Engineering blog series for Architects and others involved in building design, we have been looking at methods of fire suppression and most recently, water mist systems. In part 14, the basis for design was discussed and in part 15, those components which go into making a water mist system are outlined. 

Water mist nozzles are primarily designed to generate the very fine droplets of water necessary and to provide momentum for delivery into the fire plume. The mist itself is produced by one of four means:

- An orifice plate
- A spinner or internal swirl chamber
- Gas atomisation
- A deflector

Distribution of water mist over a prescribed floor area is not one of the features of water mist system design or performance.

In order for a water mist system to maintain the ultra-fine mist required, it is important that the tiny holes in the nozzles do not become blocked or partially impeded by debris of any kind. To this end, corrosion-resistant piping is used, most commonly stainless steel or copper. 

Some systems for low-pressure use may use larger orifice nozzles and may be found to use galvanised steel piping, although it is important that consideration of the necessity for filtration is considered in such cases.

All water mist systems must have control valves which enable the flow of water to be initiated and monitored.

The cylinders used for storage of water for the water mist system must be made of corrosion-resistant materials, as per the piping. Commonly, these are made of stainless steel or lined and at atmospheric pressure. Stored pressure with lined cylinders can lead to gas permeation behind the lining which would subsequently lead to system failure.

The pumps for a water mist system must be capable of meeting the maximum design flow and pressure and the capabilities must be assured by the provision of a dedicated power source which is reliable. A duplicate power supply may be necessary for critical hazards. 

In the case of pumps, design criteria similar to sprinkler systems may be applied, although type approved equipment is not available. For higher-pressure pumped systems, positive displacement pumps are necessary.

At installation, the pipework throughout must be thoroughly cleared of all debris and scale and a flush undertaken after installation. Testing must be undertaken to hydraulically check the pipework to 1.5 times the maximum operating pressure. The operation of the water supplies and control valves must also be functionally tested.

Open nozzle systems should be discharge tested where possible and all nozzles and strainers checked for cleanliness after.

Given the necessity for the system to remain free-flowing and unblocked, it is essential that regular inspection and maintenance be carried out on the system by individuals trained and experienced in water mist systems.

The next blog in the series will move on from fire suppression systems to look at Compartmentation. In the meantime, if you have any questions about this blog, or wish to discuss your own project with one of our fire engineers, please contact us.

Lawrence Webster Forrest has been working with their clients for over 25 years to produce innovative and exciting building projects. If you would like further information on how LWF and fire strategies could assist you, please contact Peter Gyere on 020 8668 8663.

While care has been taken to ensure that information contained in LWF's publications is true and correct at the time of publication, changes in circumstances after the time of publication may impact on the accuracy of this information.


Leave a reply

  *

  *

 


CAPTCHA Image

[ Change the image ]


*Required

Subscribe to our fire safety blogs

Bulletins
Email Format
* indicates required

FIRE SAFETY BLOGS

  • Fire Engineering Design and Risk Assessment - Compartmentation & Fire Severity - Part 10

    In LWF’s Fire Engineering blog series for Architects and others in the building design industry, we have been looking at the use of compartmentation to avoid the spread of fire. In part 9, the use of compartments with sprinkler systems was discussed and in part 10, we look at the potential severity of fires in enclosed spaces.The severity of a fire in an enclosed space is dependent upon factors such as heat leaving the...

    Read more...

  • Fire Safety for Healthcare Premises - Sprinklers - Part 44

    In LWF’s blog series for healthcare professionals, the aim is to give information on best practice of fire safety in hospitals and other healthcare premises. In part 43 of this series, we discussed cavity barriers and those areas where they are not practical for use, for fire safety reasons. In part 44, we move on to discuss the use of sprinklers in healthcare buildings. Sprinklers are not a requirement for patient areas of healthcare buildings...

    Read more...

  • Facilities Management & Fire Safety - Fire Safety Engineering - Part 1

    In LWF’s blog series for those who work in Facilities Management or who have an interest in or responsibility for fire safety, we were looking at fire safety training. In Part 1 of this series, however, we begin to review the subject of fire safety engineering. While most people reading on this subject could work out what fire safety engineering is, from the title, LWF will start by looking at the history of fire safety...

    Read more...

  • Fire Engineering Design and Risk Assessment - Compartmentation & Sprinklers - Part 9

    In LWF’s fire engineering blog series for Architects and others in the building design business, we have been looking at compartmentation and how can be used both in prescriptive and fire engineered solutions. In part 8 of this series, the provision of a fire safety strategy for a building was discussed and in part 9, we move onto how compartmentation and sprinklers work together.The effectiveness of sprinkler systems at controlling fires has had a...

    Read more...

  • Fire Safety for Healthcare Premises - Cavity Barriers and Sprinklers - Part 43

    In LWF’s blog series for healthcare professionals, the aim is to give information on best practice of fire safety in hospitals and other healthcare premises. In part 42 of this series, we looked at how cavity barriers should be installed in uninterrupted concealed spaces or cavities and also some exceptions to the rules. In part 43, we will continue looking at the use of cavity barriers in healthcare buildings.There are some instances where cavity...

    Read more...

Case Studies

The Wohl Neuroscience Institute - Fire Safety, Strategy & Engineering
Key Facts: Client: King’s Clinical Neuroscience Institute Project Manager: MACE Ltd Designers: Devereux Architects/Allies and Morrison Approximate Size: 7,400m2 Description of the Project:...

Read more..

General Bulletins

Fire - The External Risk
When we consider fire safety, our focus is normally from within, what can we do to prevent the occurrence of fire and how we can limit its damage.  Whilst this is the correct stance to take, we m...

Read more..

Technical Bulletins

Evacuation Modelling - Factor in Human Behaviour
Evacuation of buildings can be analyzed in different ways. Approved Document B (ADB) which provides guidance on meeting the requirements of the England and Wales Building Regulations with regard to fi...

Read more..

Site map | Web development London