Lawrence Webster Forrest (LWF), Fire Engineering and Fire Risk Management Consultants
Lawrence Webster Forrest (LWF), Fire Engineering and Fire Risk Management Consultants



Navigation

Client login
Forgotten password
Follow us on Twitter Follow us on Facebook Subscribe to our blog

Lawrence Webster Forrest
Legion House
Lower Road
Kenley
Surrey
CR8 5NH

Tel: +44 (0)20 8668 8663 Fax: +44 (0)20 8668 8583
E-mail: fire@lwf.co.uk

Fire Engineering Design and Risk Assessment - Sprinkler Installation Design - Part 42

Posted by LWF: 16/04/2018 11:17

In LWF’s fire engineering blog series for Architects and others in the building design industry, we have been looking at sprinkler installation design. In part 41, we started looking at how an enhanced sprinkler system in case of multiple-point fires would differ from a standard sprinkler system in design. The safeguards which must be considered for such a system including pump, electrical supply and water ‘fail-safe’. Part 42 continues from that point.

Each division of the water tank should have an emergency refill connection to be accessed by the fire service and the pump delivery manifold should be arranged in a way that allows each group of two pumps to serve an independent manifold. Each manifold will then distribute to an independent riser location.

Each riser should be arranged to serve alternate floors and be fitted with a pressure switch to signal to the pump suction manifold motorised stop valve when there is a sudden drop in pressure. The alternate floor arrangement provides an additional level of redundancy, should a failure occur in one riser, the next, alternate riser should still operate. 

A standard sprinkler system is designed to function typically using 18 sprinkler heads for up to an hour, whereas the enhanced sprinkler system possible for property protection enhancements could have 36 sprinkler heads operating on a fire floor, even when flashover has occurred, which could use up the water supply within 30 minutes. When sprinklers on other floors become operational, the water supply will run out even sooner.

In order to combat the problems raised by using so much more water than a standard sprinkler system in a much shorter space of time, the infill to the water tank should be sized to maximise the potential of the water main. This means that although the tank will not be dependent on the rate of inflow to operate under normal conditions, the option is available for extraordinary circumstances if required.

As the mechanical failure of a sprinkler riser or distribution main is a possibility, the pump suction manifold’s motorised valve will be set to close if a sudden drop in pressure is identified in any riser. This precaution allows for at least 50% of the water to remain available to the second riser.

Even when considering the possible failures or issues which may be encountered in the operation of a sprinkler system and attempting to mitigate them, there are still problems which could be encountered which would jeopardise the whole system, and in the case of a large fire, potentially the building too. The sprinkler plant room itself could potentially be breached and if the decision is taken to mitigate this risk, it would mean separate plant rooms where each room would house half of the stored water and two of the four pumps. The suction manifold would still connect the two tanks, but each set of two pumps would require separation by compartment.

In part 43 of this series, LWF will discuss domestic and residential sprinkler systems. In the meantime, if you have any questions about this blog, or wish to discuss your own project with one of our fire engineers, please contact us.

Lawrence Webster Forrest has been working with their clients for over 25 years to produce innovative and exciting building projects. If you would like further information on how LWF and fire strategies could assist you, please contact Peter Gyere on 020 8668 8663.

While care has been taken to ensure that information contained in LWF's publications is true and correct at the time of publication, changes in circumstances after the time of publication may impact on the accuracy of this information.
 


Leave a reply

  *

  *

 


CAPTCHA Image

[ Change the image ]


*Required

Subscribe to our fire safety blogs

Bulletins
Email Format
* indicates required

FIRE SAFETY BLOGS

  • Fire Engineering Design and Risk Assessment - Compartmentation & Fire Severity - Part 10

    In LWF’s Fire Engineering blog series for Architects and others in the building design industry, we have been looking at the use of compartmentation to avoid the spread of fire. In part 9, the use of compartments with sprinkler systems was discussed and in part 10, we look at the potential severity of fires in enclosed spaces.The severity of a fire in an enclosed space is dependent upon factors such as heat leaving the...

    Read more...

  • Fire Safety for Healthcare Premises - Sprinklers - Part 44

    In LWF’s blog series for healthcare professionals, the aim is to give information on best practice of fire safety in hospitals and other healthcare premises. In part 43 of this series, we discussed cavity barriers and those areas where they are not practical for use, for fire safety reasons. In part 44, we move on to discuss the use of sprinklers in healthcare buildings. Sprinklers are not a requirement for patient areas of healthcare buildings...

    Read more...

  • Facilities Management & Fire Safety - Fire Safety Engineering - Part 1

    In LWF’s blog series for those who work in Facilities Management or who have an interest in or responsibility for fire safety, we were looking at fire safety training. In Part 1 of this series, however, we begin to review the subject of fire safety engineering. While most people reading on this subject could work out what fire safety engineering is, from the title, LWF will start by looking at the history of fire safety...

    Read more...

  • Fire Engineering Design and Risk Assessment - Compartmentation & Sprinklers - Part 9

    In LWF’s fire engineering blog series for Architects and others in the building design business, we have been looking at compartmentation and how can be used both in prescriptive and fire engineered solutions. In part 8 of this series, the provision of a fire safety strategy for a building was discussed and in part 9, we move onto how compartmentation and sprinklers work together.The effectiveness of sprinkler systems at controlling fires has had a...

    Read more...

  • Fire Safety for Healthcare Premises - Cavity Barriers and Sprinklers - Part 43

    In LWF’s blog series for healthcare professionals, the aim is to give information on best practice of fire safety in hospitals and other healthcare premises. In part 42 of this series, we looked at how cavity barriers should be installed in uninterrupted concealed spaces or cavities and also some exceptions to the rules. In part 43, we will continue looking at the use of cavity barriers in healthcare buildings.There are some instances where cavity...

    Read more...

Case Studies

The Wohl Neuroscience Institute - Fire Safety, Strategy & Engineering
Key Facts: Client: King’s Clinical Neuroscience Institute Project Manager: MACE Ltd Designers: Devereux Architects/Allies and Morrison Approximate Size: 7,400m2 Description of the Project:...

Read more..

General Bulletins

Fire - The External Risk
When we consider fire safety, our focus is normally from within, what can we do to prevent the occurrence of fire and how we can limit its damage.  Whilst this is the correct stance to take, we m...

Read more..

Technical Bulletins

Evacuation Modelling - Factor in Human Behaviour
Evacuation of buildings can be analyzed in different ways. Approved Document B (ADB) which provides guidance on meeting the requirements of the England and Wales Building Regulations with regard to fi...

Read more..

Site map | Web development London