Fire Engineering Design and Risk Assessment - Firefighting & External Water Supplies - Part 30

Posted by LWF: 04/03/2019 15:10

In LWF’s blog Fire Engineering blog series for Architects and others in the building design industry, we have been exploring the subject of firefighting and those matters which should be taken into account for effective firefighting. In part 29, we discussed fire hydrants and required flow. In part 30, we will look at other external water supplies which may be available or necessary.

As a part of a building’s fire safety provision, it may be deemed necessary for a fire tank to be provided and this should be planned at the design stage when the fire protection measures are being decided.  A fire tank is a tank containing water which can be situated either above ground or below, forming part of a hydrant system. When the tank is above ground height it may feed the system through simple gravity and when it is below ground, a suction hose may be used to extract water.

In some cases, the building is situated next to open water suitable for supplying firefighting activities. Such facilities might include the sea, docks, rivers, streams, lakes (natural or man-made), reservoirs, ponds etc. A suction hose will be required in order to extract water.

When considering the capacities required from external water supplies, Approved Document B has the following to say on the subject:

Where no piped water supply is available, or there is insufficient pressure and flow in the water main, or an alternative arrangement is proposed, the alternative source of supply should be provided in accordance with the following recommendations:

(a) a charged static water tank of at least 45 000 litre capacity;

or

(b) a spring, river, canal or pond capable of providing or storing at least 45 000 litres of water at all times of the year, to which access, space and a hard-standing are available for a pumping appliance;

 or

(c) any other means of providing a water supply for firefighting operations considered appropriate by the fire and rescue authority. 

With this in mind, the capacity required is a minimum of 45 000 litres at all times and consultation with the Fire Service in the area must be undertaken.

BS 9999 (https://shop.bsigroup.com/ProductDetail?pid=000000000030357099) states that where the water supply takes the form of a static tank or dam that the capacity should be related to the size of the building and the calculated risk involved. Where there is an unlimited and guaranteed natural water source capable of providing the necessary capacity, there must be sufficient hard standing for fire appliances provided.

In Part 31 of this series, LWF will continue looking at capacities of external water supplies, before looking at the practice of water relay. In the meantime, if you have any questions about this blog, or wish to discuss your own project with one of our fire engineers, please contact us. 

Lawrence Webster Forrest has been working with their clients for over 25 years to produce innovative and exciting building projects. If you would like further information on how LWF and fire strategies could assist you, please contact Peter Gyere on 020 8668 8663.

While care has been taken to ensure that information contained in LWF's publications is true and correct at the time of publication, changes in circumstances after the time of publication may impact on the accuracy of this information.

Leave a reply

  *

  *

 


CAPTCHA Image

[ Change the image ]


*Required

Subscribe to our fire safety blogs

Bulletins
Email Format
* indicates required

FIRE SAFETY BLOGS

  • Fire Engineering Design and Risk Assessment - Firefighting & Internal Water Supplies - Part 32

    In LWF’s Fire Engineering blog series for Architects and others involved in the building design business, we have been looking at fire safety engineering and, most recently, firefighting. In part 31, we looked at the recommendations made regarding water capacity for any open water used for firefighting purposes and discussed relaying water to the place of fire origin. In part 32, we look at internal water supplies designed for the purpose of firefighting.Fire mains...

    Read more...

  • Fire Safety for Healthcare Premises - Fire Safety Policies - Part 66

    In LWF’s blog series for healthcare professionals, our aim is to give information on best practice of fire safety in hospitals and other healthcare premises. In part 65, LWF considered some of the many important elements when considering general fire safety in a healthcare building, including the provision of alternative escape routes and the potentially unpredictable nature of human behaviour in a fire situation. In part 66, we look at fire safety policies.Clearly-defined fire...

    Read more...

  • Facilities Management & Fire Safety - Insurers & Property Protection - Part 13

    In LWF’s blog series for those who work in Facilities Management, or who have an interest in or responsibility for fire safety, we have been looking at the role of insurers in property protection. In part 12, we looked at the increase of liability insurance which coincided with the introduction of the Employers’ Liability Act – designed to put into place a system whereby a person injured at work could claim against his employer for...

    Read more...

  • Fire Engineering Design and Risk Assessment - Firefighting & External Water Supplies - Part 31

    In LWF’s Fire Engineering blog series for Architects and others in the building design business, we have been looking at the subject of fire safety engineering and most recently, firefighting. In part 30, we considered additional external water supplies which may be used instead of hydrants. In part 31, we discuss capacities and water relay.

    Read more...

  • Fire Safety for Healthcare Premises - Fire Safety Measures for Healthcare Buildings - Part 65

    In LWF’s blog series for healthcare professionals, our aim is to give information on best practice of fire safety in hospitals and other healthcare premises. In part 64, LWF discussed the threat to life, continued treatment and the loss of potentially expensive equipment if a fire was to occur and stated the fact that active and passive fire protection methods, as well as fire prevention must be of the utmost importance to healthcare venues. In...

    Read more...

Case Studies

Duke of York, Victoria Street, London
The Duke of York is a busy pub in central London, used by commuters and theatre-goers alike.  In 2013, the pub was demolished in order to facilitate the London Underground Victoria Station Upgrad...

Read more..

General Bulletins

Fire - The External Risk
When we consider fire safety, our focus is normally from within, what can we do to prevent the occurrence of fire and how we can limit its damage.  Whilst this is the correct stance to take, we m...

Read more..

Technical Bulletins

Evacuation Modelling - Factor in Human Behaviour
Evacuation of buildings can be analyzed in different ways. Approved Document B (ADB) which provides guidance on meeting the requirements of the England and Wales Building Regulations with regard to fi...

Read more..

Site map | Web development Croydon