Fire Engineering Design and Risk Assessment - Firefighting & External Water Supplies - Part 27

Posted by LWF: 12/02/2019 11:32

In LWF’s Fire Engineering blog series for Architects and others in the building design business, we have been looking at fire safety engineering. In part 26, we looked at how the choice of fire hydrant can affect the efficiency of delivery and by working out the additional time required to prime an underground hydrant when compared to a pillar hydrant with instantaneous couplings, it was established there could be as much as 2 minutes delay on the former. In part 27, LWF will continue to discuss the provision and placing of hydrants for firefighting purposes and the importance of water pressure to firefighting.
A formula can be used to work out the time taken to get additional water supplies, as follows:

t – (Wp – Wh) / D

t is the time available to obtain additional water supplies in minutes, Wp is the quantity of water in the pumping appliance tank in litres, Wh is the quantity of water in the hose lines from pump to branch in litres and D is the discharge rate from a nozzle in 1/min.

The standards relating to hydrant positioning have changed over the years, with requirements made depending on the risk and fire-fighting requirements of a building. For example, a building fitted with a rising main requires a fire hydrant within 90 m of the parking position of the fire appliance. The fire appliance must be able to park within 18 m of the rising main inlet point. These distances are based on standard firefighting hose lengths, i.e. 25 m, so based on the above, it is designed that a fire appliance can park, use one length of hose to charge the rising main, with 4 lengths used to replenish the fire appliance. This would leave remaining lengths of hose to be used for internal fire- fighting. Hydrant coverage should be reviewed and considered as part of the buildings fire risk assessment. 

Some locations in the UK are subject to the installation of pressure-reducing valves meaning that the water pressure available is insufficient for firefighting purposes. There are currently two methods used by the Fire Service to overcome these limitations. The first is that they are able to identify upstream hydrants which produce sufficient water pressure and relay the water to the site of the fire with the use of additional pumping appliances. 

The second method of overcoming the pressure-reducing valves which lower the water pressure is that the Fire Service request the attendance of a turncock from the water supply company which opens the valves to increase flow. 
When neither of these options are possible, the Fire Service may resort to collector pumping and large-scale water relay using hoses. 

In part 28 of this series, LWF will look at how to assess the required flow from fire hydrants. In the meantime, if you have any questions about this blog, or wish to discuss your own project with one of our fire engineers, please contact us. 

Lawrence Webster Forrest has been working with their clients for over 25 years to produce innovative and exciting building projects. If you would like further information on how LWF and fire strategies could assist you, please contact Peter Gyere on 020 8668 8663.

While care has been taken to ensure that information contained in LWF's publications is true and correct at the time of publication, changes in circumstances after the time of publication may impact on the accuracy of this information.

Leave a reply

  *

  *

 


CAPTCHA Image

[ Change the image ]


*Required

Subscribe to our fire safety blogs

Bulletins
Email Format
* indicates required

FIRE SAFETY BLOGS

  • Fire Engineering Design and Risk Assessment - Firefighting & Rising Water Mains - Part 36

    In LWF’s fire engineering blog series for Architects and others in the building design business, we have been talking about firefighting and rising water mains in buildings. In part 35, we began to discuss wet rising water mains and in part 36 we will continue looking at that subject before considering horizontal mains, also known as internal hydrants, which are seen more commonly in buildings with large floor area.It was established in part 35...

    Read more...

  • Fire Safety for Healthcare Premises - Fire Safety Audits - Part 70

    In LWF’s blog series for healthcare professionals, the aim is to give information on best practice of fire safety in hospitals and other healthcare premises. In part 69, we discussed the management of staffing levels and in addition to the number of staff available, it was important that each and every staff member had adequate training in fire and evacuation issues. In part 70, we will discuss fire safety audits and what arrangements should be...

    Read more...

  • Facilities Management & Fire Safety - Business Continuity Insurance - Part 17

    In LWF’s blog series for those who work in Facilities Management or who have an interest in or responsibility for fire safety, we have been looking at how businesses are protected against interruption from fire. In part 16, we began an overview of the history of consequential loss insurance, which only came into being around 1900, long after life and property protection insurance.  In part 17, we continue from the 1960s.Although the increase in...

    Read more...

  • Fire Engineering Design and Risk Assessment - Firefighting & Rising Water Mains - Part 35

    In LWF’s Fire Engineering blog series for Architects and others in the building design business, we have been looking at those provisions which can be made to assist firefighting in case of a fire. In part 34, we commenced looking at wet rising mains and noted that while they can be permanently connected to water mains, it is more common to see the systems connected to a water tank with a pump or gravity feed,...

    Read more...

  • Fire Safety for Healthcare Premises - Fire Safety & Staffing Levels - Part 69

    In LWF’s blog series for healthcare professionals, the aim is to give information on best practice of fire safety in hospitals and other healthcare premises. In part 68, LWF discussed staffing levels in terms of fire safety and the importance of the staff in attendance having sufficient fire safety training. In part 69, we will continue looking at staffing levels and fire safety concerns.The management of any healthcare venue must consider and agree what...

    Read more...

Case Studies

Brentwood Town Hall Redevelopment
The redevelopment of Brentwood Town Hall included renovating the existing five storey property to provide police and council offices, a community hub and lettable office space across the basement, gro...

Read more..

General Bulletins

Fire - The External Risk
When we consider fire safety, our focus is normally from within, what can we do to prevent the occurrence of fire and how we can limit its damage.  Whilst this is the correct stance to take, we m...

Read more..

Technical Bulletins

Evacuation Modelling - Factor in Human Behaviour
Evacuation of buildings can be analyzed in different ways. Approved Document B (ADB) which provides guidance on meeting the requirements of the England and Wales Building Regulations with regard to fi...

Read more..

Site map | Web development Croydon