Fire Engineering Design and Risk Assessment - Firefighting & External Water Supplies - Part 22

Posted by LWF: 10/01/2019 12:48

In LWFs fire engineering blog series for Architects and others involved in building design, we have been looking at the subject of firefighting. In part 21, the issue of whether a building needs to supply a source of water for the Fire Service to use upon attending a fire was discussed. In part 22, we continue looking at the regulations dealing with water hydrants.

In the UK, BS 5306:1 was published in 1976 (and withdrawn and updated in 2006, replaced by BS 5306:1-2006 and BS 9990:2006 and dealt with water hydrant systems. It recommended that fire hydrants are installed on a ring fire main system and are positioned not more than 70 metres from an entry point of any building on site and not more than 150 metres apart from each other. They should be no closer than 6 metres to the building.

In 2002, following a study, the Local Government Association and Water UK produced a document titled ‘National guidance document on the provision of water for fire fighting’ (PDF) which linked flow rates of water in litres per second to differing structures. It showed that there were significant variations in flow rate even within the same structure groups. It went on to say that if the water supply is not in the control of the building owner (e.g. an owned lake) it is only the water undertaking which can vary the flow from a main.

Another source from the UK – Approved Document B in subsection 15.7 states:

‘Where a building, which has a compartment of 280 m2 in area, is being erected more than 100 metres from an existing fire hydrant, additional hydrants should be provided as follows:

(a) Buildings provided with fire mains - hydrants should be provided within 90 m of dry fire main inlets.

(b) Buildings not provided with fire mains - hydrants should be provided within 90 m of an entry point to the building and not more than 90 m apart.

The implication is that the building owner should arrange and pay for the hydrants as indicated, although it must, once again, be noted that there is no legal requirement for a building owner to provide water sources for fire-fighting by the Fire Service.

LWF’s discussion about issues surrounding fire hydrants and the provision of them will continue in part 23 of this series. In the meantime, if you have any questions about this blog, or wish to discuss your own project with one of our fire engineers, please contact us. 

Lawrence Webster Forrest has been working with their clients for over 25 years to produce innovative and exciting building projects. If you would like further information on how LWF and fire strategies could assist you, please contact Peter Gyere on 020 8668 8663.

While care has been taken to ensure that information contained in LWF's publications is true and correct at the time of publication, changes in circumstances after the time of publication may impact on the accuracy of this information.

Leave a reply

  *

  *

 


CAPTCHA Image

[ Change the image ]


*Required

Subscribe to our fire safety blogs

Bulletins
Email Format
* indicates required

FIRE SAFETY BLOGS

  • Fire Safety for Healthcare Premises - Fire Safety Training for Staff - Part 80

    In LWFs blog series for healthcare professionals, the aim is to give information on best practice of fire safety in hospitals and other healthcare premises. In part 79, LWF began to discuss fire safety training for staff in healthcare premises and in part 80, we continue from that point with more information on who should attend training and what it should comprise.Fire safety training for staff should have the aim of producing awareness and...

    Read more...

  • Facilities Management & Fire Safety - Community Fire Safety - Part 6

    In LWF’s blog series for those who work in Facilities Management, or who have an interest in or responsibility for fire safety, we have been looking at community fire safety. In part 5, we looked at how government initiatives and programmes have impacted fire safety in homes and schools, including the home fire risk checks undertaken by the Fire Service.  In part 6, we will continue discussing community fire safety by looking at some of...

    Read more...

  • Fire Engineering Design and Risk Assessment - Firefighting Shafts - Part 46

    In LWF’s recent Fire Engineering blog series for Architects and others in the building design industry, we have been looking at Firefighting. In part 45, we looked at recommendations for the provision of firefighting shafts contained in Approved Document B and BS 9999. In part 46, we consider what those documents have to say on general design considerations for firefighting shafts.Approved Document B and BS...

    Read more...

  • Fire Safety for Healthcare Premises - Fire Safety Training for Staff - Part 79

    In LWFs blog series for healthcare professionals, the aim is to give information on best practice of fire safety in hospitals and other healthcare premises. In part 78, LWF looked at fire precautions in underground locations. In part 79, we discuss fire safety training for staff in healthcare premises.  The effective management of fire safety training for all staff in healthcare venues is an important area of fire safety management. It is also a statutory...

    Read more...

  • Facilities Management & Fire Safety - Community Fire Safety - Part 5

    In LWF’s blog series for those who work in Facilities Management, or who have an interest in or responsibility for fire safety we have been looking at domestic fire safety and the related initiatives in the UK. In part 4, we discussed how useful fire safety education for children has been in influencing fire-safe behaviour in the home. In part 5, we consider home fire risk checks before looking at the evidence of successful community...

    Read more...

Case Studies

Brentwood Town Hall Redevelopment
The redevelopment of Brentwood Town Hall included renovating the existing five storey property to provide police and council offices, a community hub and lettable office space across the basement, gro...

Read more..

General Bulletins

Fire - The External Risk
When we consider fire safety, our focus is normally from within, what can we do to prevent the occurrence of fire and how we can limit its damage.  Whilst this is the correct stance to take, we m...

Read more..

Technical Bulletins

Evacuation Modelling - Factor in Human Behaviour
Evacuation of buildings can be analyzed in different ways. Approved Document B (ADB) which provides guidance on meeting the requirements of the England and Wales Building Regulations with regard to fi...

Read more..

Site map | Web development Croydon