Fire Engineering Design and Risk Assessment - Firefighting & External Water Supplies - Part 22

Posted by LWF: 10/01/2019 12:48

In LWFs fire engineering blog series for Architects and others involved in building design, we have been looking at the subject of firefighting. In part 21, the issue of whether a building needs to supply a source of water for the Fire Service to use upon attending a fire was discussed. In part 22, we continue looking at the regulations dealing with water hydrants.

In the UK, BS 5306:1 was published in 1976 (and withdrawn and updated in 2006, replaced by BS 5306:1-2006 and BS 9990:2006 and dealt with water hydrant systems. It recommended that fire hydrants are installed on a ring fire main system and are positioned not more than 70 metres from an entry point of any building on site and not more than 150 metres apart from each other. They should be no closer than 6 metres to the building.

In 2002, following a study, the Local Government Association and Water UK produced a document titled ‘National guidance document on the provision of water for fire fighting’ (PDF) which linked flow rates of water in litres per second to differing structures. It showed that there were significant variations in flow rate even within the same structure groups. It went on to say that if the water supply is not in the control of the building owner (e.g. an owned lake) it is only the water undertaking which can vary the flow from a main.

Another source from the UK – Approved Document B in subsection 15.7 states:

‘Where a building, which has a compartment of 280 m2 in area, is being erected more than 100 metres from an existing fire hydrant, additional hydrants should be provided as follows:

(a) Buildings provided with fire mains - hydrants should be provided within 90 m of dry fire main inlets.

(b) Buildings not provided with fire mains - hydrants should be provided within 90 m of an entry point to the building and not more than 90 m apart.

The implication is that the building owner should arrange and pay for the hydrants as indicated, although it must, once again, be noted that there is no legal requirement for a building owner to provide water sources for fire-fighting by the Fire Service.

LWF’s discussion about issues surrounding fire hydrants and the provision of them will continue in part 23 of this series. In the meantime, if you have any questions about this blog, or wish to discuss your own project with one of our fire engineers, please contact us. 

Lawrence Webster Forrest has been working with their clients for over 25 years to produce innovative and exciting building projects. If you would like further information on how LWF and fire strategies could assist you, please contact Peter Gyere on 020 8668 8663.

While care has been taken to ensure that information contained in LWF's publications is true and correct at the time of publication, changes in circumstances after the time of publication may impact on the accuracy of this information.

Leave a reply

  *

  *

 


CAPTCHA Image

[ Change the image ]


*Required

Subscribe to our fire safety blogs

Bulletins
Email Format
* indicates required

FIRE SAFETY BLOGS

  • Fire Engineering Design and Risk Assessment - Firefighting & External Water Supplies - Part 24

    In LWF’s fire engineering blog series for Architects and other professionals involved in building design, we have been looking at firefighting and, most recently, the provisions that should be made for the Fire Service to attend and put out a fire. In part 23, we looked at the requirements and recommendations relating to the provision of fire hydrants and we continue from that point in part 24.The original standards for the installation of water...

    Read more...

  • Fire Safety for Healthcare Premises - Access & Facilities for the Fire Service - Part 58

    In LWFs blog series for healthcare professionals, the aim is to give information on best practice of fire safety in hospitals and other healthcare premises. In part 57 of this series, LWF looked at what access and facilities must be provided for the Fire Service attending a fire at a healthcare venue. In part 58, we will continue from that point by looking at the number and location of fire-fighting shafts required in those healthcare...

    Read more...

  • Facilities Management & Fire Safety - Insurers & Property Protection - Part 5

    In LWF’s blog series for those professionals who work in facilities management or who have an interest in or responsibility for fire safety, we have been looking at property protection and the role of the insurer. In part 4, some of the history that led to property insurance from fire was given and in part 5, we will continue looking at how different the early insurers could be from what we know today.While the...

    Read more...

  • Fire Engineering Design and Risk Assessment - Firefighting & External Water Supplies - Part 23

    In LWFs fire engineering blog series for Architects and others involved in building design, we have been looking at the subject of firefighting. In part 22, we gave information on some of the regulations and guidance documents which deal with the issue of provision of fire hydrants. In part 23, we continue from that point by looking at who should provide them and where they should be placed in relation to the building.

    Read more...

  • Fire Safety for Healthcare Premises - Access & Facilities for the Fire Service - Part 57

    In LWFs blog series for healthcare professionals, the aim is to give information on best practice of fire safety in hospitals and other healthcare premises. In part 56 of this series, LWF spent time looking at the access required by Fire and Rescue Service vehicles to healthcare buildings not fitted with fire mains. In part 57, LWF will continue looking at those measures which should be taken to ensure the Fire Service has access to...

    Read more...

Case Studies

The Wohl Neuroscience Institute - Fire Safety, Strategy & Engineering
Key Facts: Client: King’s Clinical Neuroscience Institute Project Manager: MACE Ltd Designers: Devereux Architects/Allies and Morrison Approximate Size: 7,400m2 Description of the Project:...

Read more..

General Bulletins

Fire - The External Risk
When we consider fire safety, our focus is normally from within, what can we do to prevent the occurrence of fire and how we can limit its damage.  Whilst this is the correct stance to take, we m...

Read more..

Technical Bulletins

Evacuation Modelling - Factor in Human Behaviour
Evacuation of buildings can be analyzed in different ways. Approved Document B (ADB) which provides guidance on meeting the requirements of the England and Wales Building Regulations with regard to fi...

Read more..

Site map | Web development London