Facilities Management & Fire Safety - Calculating ASET as per BS 7974 - Part 8

Posted by LWF: 06/12/2018 12:40

In LWFs blog series for those who work in Facilities Management or who have an interest in or responsibility for fire safety, we have been looking at the concept of fire safety engineering. In part 7, we looked at BS 7974 and the framework it provides to achieve an engineered approach to fire safety in buildings and escape time. In part 8, LWF will consider escape time by breaking it down into the different components which it comprises.

The escape time is considered by sub-dividing events into components, as follows:

Detection Time

The time span between fire ignition and discovery of a fire.


Time to sound alarm 

This can be expected to take up to 10 seconds if the detection and alarm system are automatic, due to current standards. Substantially longer delays can be expected if the fire is detected by a person or people, due in part to a reticence by individuals to sound the fire alarm even if they can see fire and it has been known that people will delay sounding a fire alarm to undertake other tasks too.


Recognition time

After the fire alarm has sounded, occupants of the building sometimes continue with the task they were previously undertaking, such as eating a meal, working on something, shopping etc. Improvements upon time taken to reach recognition can be achieved with good fire safety management and training within the building.


Response time

After occupants have recognised there is a fire situation and they need to respond to the alarm signal or simply their knowledge that there is a fire, there is a further delay known as the ‘response time’ before people begin to move towards an exit. The duration of the response time can vary significantly from a few seconds to grab their phone or bag to a longer period during which they might turn off machinery, look for family members or lock a cash till, for instance.

It should be noted that the vast majority of actions undertaken during the response time are not recommended or accepted but should still be taken into account by the building owner/occupier when considering timings.

The escape time has further elements, known as ‘pre-movement time’ and ‘travel time’. Both elements will be discussed by LWF in part 9 of this series. In the meantime, if you have any queries about your own facilities or wish to discuss this blog series, please contact Peter Gyere in the first instance on 0208 668 8663.

Lawrence Webster Forrest is a fire engineering consultancy based in Surrey with over 25 years' experience, which provides a wide range of consultancy services to professionals involved in the design, development and construction and operation of buildings. 

While care has been taken to ensure that information contained in LWF's publications is true and correct at the time of publication, changes in circumstances after the time of publication may impact on the accuracy of this information.

Leave a reply

  *

  *

 


CAPTCHA Image

[ Change the image ]


*Required

Subscribe to our fire safety blogs

Bulletins
Email Format
* indicates required

FIRE SAFETY BLOGS

  • Fire Engineering Design and Risk Assessment - Firefighting & External Water Supplies - Part 22

    In LWFs fire engineering blog series for Architects and others involved in building design, we have been looking at the subject of firefighting. In part 21, the issue of whether a building needs to supply a source of water for the Fire Service to use upon attending a fire was discussed. In part 22, we continue looking at the regulations dealing with water hydrants.In the UK, BS 5306:1 was published in 1976 (and withdrawn...

    Read more...

  • Fire Safety for Healthcare Premises - Access & Facilities for the Fire Service - Part 56

    In LWF’s blog series for healthcare professionals, the aim is to give information on best practice of fire safety in hospitals and other healthcare premises. In part 55 of this series, we began looking at the importance of access by road for the Fire Service and which entrances should be used for their access. In part 56, LWF will continue looking at those measures which should be taken to ensure the Fire Service has access...

    Read more...

  • Facilities Management & Fire Safety - Fire Safety Objectives - Part 3

    In LWFs blog series for those who work in Facilities Management, or who have an interest in or responsibility for fire safety, we have been looking at property protection and the insurer. In part 2, it was ascertained that while there is a legal requirement for buildings to be fire safe in order to ensure the safe evacuation of the building occupants, there is no legal requirement for precautions which are designed for the protection...

    Read more...

  • Fire Engineering Design and Risk Assessment - Firefighting & External Water Supplies - Part 21

    In LWF’s fire engineering blog series for Architects and others involved in building design we have been looking at firefighting. In part 20, an outline of how the water carried by a fire engine is used with the hoses to provide a limited time supply of water to fight a fire. In part 21, we continue from that point.As a fire engine can only carry a limited amount of water, a large fire will...

    Read more...

  • Fire Safety for Healthcare Premises - Access & Facilities for the Fire Service - Part 55

    In LWFs blog series for healthcare professionals, the aim is to give information on best practice of fire safety in hospitals and other healthcare premises. In part 54 of this series, we finished our discussion on ventilation for car parks as part of healthcare buildings. In part 55, we move on to look at the provision of access and facilities for the Fire Service both in terms of general requirements and those particular to healthcare...

    Read more...

Case Studies

The Wohl Neuroscience Institute - Fire Safety, Strategy & Engineering
Key Facts: Client: King’s Clinical Neuroscience Institute Project Manager: MACE Ltd Designers: Devereux Architects/Allies and Morrison Approximate Size: 7,400m2 Description of the Project:...

Read more..

General Bulletins

Fire - The External Risk
When we consider fire safety, our focus is normally from within, what can we do to prevent the occurrence of fire and how we can limit its damage.  Whilst this is the correct stance to take, we m...

Read more..

Technical Bulletins

Evacuation Modelling - Factor in Human Behaviour
Evacuation of buildings can be analyzed in different ways. Approved Document B (ADB) which provides guidance on meeting the requirements of the England and Wales Building Regulations with regard to fi...

Read more..

Site map | Web development London